FTC GRP PANEL TYPE WATER STORAGE TANKS -
STEEL TOWER |
 |
|
|
Steel
Tower |
 |
|
. |
-
Our FTC GRP Panel type water tank can easily be
installed on a Steel tower which consists of
Truss or lattice type construction in a
standard module, pre-welded and perforated,
and designed to be loaded in container.
Design Criteria
|
1. Wind Velocity |
60m/sec |
|
2. Allowable Strength (Short time) |
|
|
a) Steel (tensile)
|
2.4 ton/cm2 (23.5KN/cm2) |
|
(Japanese Standard SS41)
|
|
|
b) Concrete (Comprehensive)
|
0.18 ton/cm2 (1.76KN/cm2) |
|
c) Anchor Bolt
|
|
|
High Tension
|
10 ton/cm2 (98KN/cm2) |
|
3. Seismic Coefficient |
K = 0.3G |
(For more severe earthquake conditions, the
factor can be increased to between 0.6G and
1.0G). |
© 1999 - 2008 Fiber Technology
Corporation, Inc. VA, USA
|
|
|
|
|
|
|