FTC GRP PANEL TYPE WATER STORAGE TANKS - STEEL TOWER

 

Steel Tower

.
  • Our FTC GRP Panel type water tank can easily be installed on a Steel tower which consists of Truss or lattice type construction in a standard module, pre-welded and perforated, and designed to be loaded in container.

  • At site, those modules will require simple bolting together, to form the required steel tower.

  • All towers are designed using latest steel technology. Design criteria have been established based on internationally accepted standards for both normal (Static) and dynamic seismic loads. Local site condition factors are given careful consideration as well. The design criteria and site condition factors are tabulated below.

Design Criteria

1. Wind Velocity 60m/sec
2. Allowable Strength (Short time)  
    a) Steel (tensile)
2.4 ton/cm2 (23.5KN/cm2)
        (Japanese Standard SS41)
 
    b) Concrete (Comprehensive)
0.18 ton/cm2 (1.76KN/cm2)
    c) Anchor Bolt
 
        High Tension
10 ton/cm2 (98KN/cm2)
3. Seismic Coefficient K = 0.3G

(For more severe earthquake conditions, the factor can be increased to between 0.6G and 1.0G).